SU Rung
This is the upgrade slotted rung for all steel ladder cable trays. SU rungs are installed alternating slot up and slot down.
| RUNG TYPE | MECHANICAL PROPERTIES | |
SU |
SLOTTED† | Minumum thickness = 0.120" Moment of Inertia: Ix = 0.0531 in4 Section Modulus: Sx = 0.0921 in3 |
| RUNG SPACING |
LOAD TABLE |
SAFE LOAD LIMITS (LBS/FT) | ||||||||
| TRAY WIDTH (IN.) | ||||||||||
| 6 | 9 | 12 | 18 | 24 | 30 | 36 | 42 | 48 | ||
| 6" | 1 |
3999 | 3999 | 3066 | 2044 | 1533 | 1226 | 1022 | 876 | 766 |
2 |
3999 | 3999 | 3066 | 2044 | 1499 | 1040 | 733 | 514 | 350 | |
| 9" | 1 |
3999 | 2725 | 2044 | 1363 | 1022 | 818 | 681 | 584 | 511 |
2 |
3999 | 2725 | 2044 | 1363 | 1000 | 693 | 489 | 343 | 233 | |
| 12"* | 1 |
3066 | 2044 | 1533 | 1022 | 766 | 613 | 511 | 438 | 383 |
2 |
3066 | 2044 | 1533 | 1022 | 750 | 520 | 366 | 257 | 175 | |
| 18" | 1 |
2044 | 1363 | 1022 | 681 | 511 | 409 | 341 | 292 | 255 |
2 |
2044 | 1363 | 1022 | 681 | 500 | 347 | 244 | 171 | 117 | |
Safe Load/Cable Load Only: Allowable uniformly-distributed cable load expressed in lbs/linear foot of tray length, based on the load carrying capability of the rung with a safety factor of 1.5. To convert Safe Load/Cable Load Only to reflect a safety factor of 2.0, multiply the safe loads shown by 0.75.
Safe Load / Cable Load +200 lbs: Allowable uniformly-distributed cable load expressed in lbs/linear foot of tray length, based on the load carrying capability of the rung with a 200 lb. concentrated static load applied at the center of the rung, without collapse.
Will not support a 200 lb. concentrated static load applied at the center of the rung.
[XX] Two digit code in the safe load limit tables indicates recommended rung option for specified width.
* Single rung load capacity: The data shown for 12" rung spacing is equivalent to the load capacity of the single rung.
† Slotted rungs are installed alternating slot up and slot down.