RS Rung
This rung is available for steel ladder tray systems for extremely heavy load applications. This profile will accept strut fasteners and accessories. RS rungs are installed alternating slot up and slot down
| RUNG TYPE | MECHANICAL PROPERTIES | |
RS |
SLOTTED† | Minumum thickness = 0.120" Moment of Inertia: 1x = 0.1848 in4 Section Modulus: Sx = 0.2040 in3 |
| RUNG SPACING |
LOAD TABLE |
SAFE LOAD LIMITS (LBS/FT) | ||||||||
| TRAY WIDTH (IN.) | ||||||||||
| 6 | 9 | 12 | 18 | 24 | 30 | 36 | 42 | 48 | ||
| 6" | 1 |
9999 | 9991 | 7494 | 4996 | 3747 | 2997 | 2498 | 2141 | 1873 |
2 |
9999 | 9991 | 7494 | 4996 | 3747 | 2997 | 2498 | 2141 | 1873 | |
| 9" | 1 |
9991 | 6661 | 4996 | 3330 | 2498 | 1998 | 1665 | 1427 | 1249 |
2 |
9991 | 6661 | 4996 | 3330 | 2498 | 1998 | 1665 | 1427 | 1249 | |
| 12"* | 1 |
7494 | 4996 | 3747 | 2498 | 1873 | 1499 | 1249 | 1071 | 937 |
2 |
7494 | 4996 | 3747 | 2498 | 1873 | 1499 | 1249 | 1071 | 937 | |
| 18" | 1 |
4996 | 3330 | 2498 | 1665 | 1249 | 999 | 833 | 714 | 624 |
2 |
4996 | 3330 | 2498 | 1665 | 1249 | 999 | 833 | 714 | 624 | |
Safe Load/Cable Load Only: Allowable uniformly-distributed cable load expressed in lbs/linear foot of tray length, based on the load carrying capability of the rung with a safety factor of 1.5. To convert Safe Load/Cable Load Only to reflect a safety factor of 2.0, multiply the safe loads shown by 0.75.
Safe Load / Cable Load +200 lbs: Allowable uniformly-distributed cable load expressed in lbs/linear foot of tray length, based on the load carrying capability of the rung with a 200 lb. concentrated static load applied at the center of the rung, without collapse.
Will not support a 200 lb. concentrated static load applied at the center of the rung.
[XX] Two digit code in the safe load limit tables indicates recommended rung option for specified width.
* Single rung load capacity: The data shown for 12" rung spacing is equivalent to the load capacity of the single rung.
† Slotted rungs are installed alternating slot up and slot down.