HL Rung
This is the standard solid rung for the following steel cable trays, up to 24" wide: NEMA Class 12B and 12C ladder and ventilated/trough trays with flange-in side rails. NEMA Class 20A, 20B and 20C, mill galvanized, ladder and ventilated/trough trays.
| RUNG TYPE | MECHANICAL PROPERTIES | |
HL |
SOLID | Thickness = 0.038" Moment of Inertia: Ix = 0.0143 in4 Section Modulus: Sx = 0.0374 in3 |
| RUNG SPACING |
LOAD TABLE |
SAFE LOAD LIMITS (LBS/FT) | ||||||||
| TRAY WIDTH (IN.) | ||||||||||
| 6 | 9 | 12 | 18 | 24 | 30 | 36 | 42 | 48 | ||
| 5" | 1 |
3351 | 2234 | 1676 | 1117 | 838 | HH | HH | SU | SU |
2 |
3351 | 2234 | 1480 | 667 | 260 | HH | HH | SU | SU | |
| 6" | 1 |
2793 | 1862 | 1396 | 931 | 698 | HH | HH | SU | SU |
2 |
2793 | 1862 | 1233 | 556 | 217 | HH | HH | SU | SU | |
| 9" | 1 |
1862 | 1241 | 931 | 621 | 465 | HH | HH | SU | SU |
2 |
1862 | 1241 | 822 | 370 | 144 | HH | HH | SU | SU | |
| 12" | 1 |
1396 | 931 | 698 | 465 | 349 | HH | HH | SU | SU |
2 |
1396 | 931 | 617 | 278 | 108 | HH | HH | SU | SU | |
Safe Load/Cable Load Only: Allowable uniformly-distributed cable load expressed in lbs/linear foot of tray length, based on the load carrying capability of the rung with a safety factor of 1.5. To convert Safe Load/Cable Load Only to reflect a safety factor of 2.0, multiply the safe loads shown by 0.75.
Safe Load / Cable Load +200 lbs: Allowable uniformly-distributed cable load expressed in lbs/linear foot of tray length, based on the load carrying capability of the rung with a 200 lb. concentrated static load applied at the center of the rung, without collapse.
Will not support a 200 lb. concentrated static load applied at the center of the rung.
[XX] Two digit code in the safe load limit tables indicates recommended rung option for specified width.
* Single rung load capacity: The data shown for 12" rung spacing is equivalent to the load capacity of the single rung.